Skip to content
AirPermitHub

40 CFR Part 60, Subpart Db

NSPS Subpart Db: Industrial-Commercial-Institutional Steam Generating Units

Subpart Db—Standards of Performance for Industrial-Commercial-Institutional Steam Generating Units
Rule text from eCFRLast amended in eCFR 2019-08-16

Where this text comes from

Citation
40 CFR Part 60, Subpart Db
Official title
Subpart Db—Standards of Performance for Industrial-Commercial-Institutional Steam Generating Units
Text as of
eCFR current through 2026-10-28, retrieved 2026-10-30
Latest amendment
2019-08-16
Source note
72 FR 32742, June 13, 2007, unless otherwise noted.

Headings and quoted sections on this page are copied from the eCFR text of Subpart Db without changes. AirPermitHub checks eCFR every week and reviews any change before publishing it, so this page can trail eCFR by a few days. eCFR is maintained by the Office of the Federal Register and the Government Publishing Office. It is not an official legal edition of the CFR, and it does not show how an agency has applied the rule in a permit.

Where to look in Subpart Db

Sections sorted by the words in their eCFR headings. Read the full section before relying on it; requirements often sit in more than one place.

Who is covered
§ 60.40b
Standards and limits
§ 60.42b§ 60.43b§ 60.44b
Showing compliance
§ 60.45b§ 60.46b
Tests, methods, and calculations
§ 60.45b§ 60.46b
Notifications, reports, records
§ 60.49b
Definitions
§ 60.41b
Who implements it
§ 60.40b

Who the subpart covers, in the rule's own words

The sections that set out what the subpart applies to, quoted in full from eCFR. Dates, sizes, and other figures are the rule's, not AirPermitHub's.

§ 60.40b Applicability and delegation of authority.

Open in eCFR

(a) The affected facility to which this subpart applies is each steam generating unit that commences construction, modification, or reconstruction after June 19, 1984, and that has a heat input capacity from fuels combusted in the steam generating unit of greater than 29 megawatts (MW) (100 million British thermal units per hour (MMBtu/hr)).

(b) Any affected facility meeting the applicability requirements under paragraph (a) of this section and commencing construction, modification, or reconstruction after June 19, 1984, but on or before June 19, 1986, is subject to the following standards:

(1) Coal-fired affected facilities having a heat input capacity between 29 and 73 MW (100 and 250 MMBtu/hr), inclusive, are subject to the particulate matter (PM) and nitrogen oxides (NOX) standards under this subpart.

(2) Coal-fired affected facilities having a heat input capacity greater than 73 MW (250 MMBtu/hr) and meeting the applicability requirements under subpart D (Standards of performance for fossil-fuel-fired steam generators; § 60.40) are subject to the PM and NOX standards under this subpart and to the sulfur dioxide (SO2) standards under subpart D (§ 60.43).

(3) Oil-fired affected facilities having a heat input capacity between 29 and 73 MW (100 and 250 MMBtu/hr), inclusive, are subject to the NOX standards under this subpart.

(4) Oil-fired affected facilities having a heat input capacity greater than 73 MW (250 MMBtu/hr) and meeting the applicability requirements under subpart D (Standards of performance for fossil-fuel-fired steam generators; § 60.40) are also subject to the NOX standards under this subpart and the PM and SO2 standards under subpart D (§§ 60.42 and 60.43).

(c) Affected facilities that also meet the applicability requirements under subpart J or subpart Ja of this part are subject to the PM and NOX standards under this subpart and the SO2 standards under subpart J or subpart Ja of this part, as applicable.

(d) Affected facilities that also meet the applicability requirements under subpart E (Standards of performance for incinerators; § 60.50) are subject to the NOX and PM standards under this subpart.

Show the rest of § 60.40b (12 more paragraphs)

(e) Steam generating units meeting the applicability requirements under subpart Da (Standards of performance for electric utility steam generating units; § 60.40Da) are not subject to this subpart.

(f) Any change to an existing steam generating unit for the sole purpose of combusting gases containing total reduced sulfur (TRS) as defined under § 60.281 is not considered a modification under § 60.14 and the steam generating unit is not subject to this subpart.

(g) In delegating implementation and enforcement authority to a State under section 111(c) of the Clean Air Act, the following authorities shall be retained by the Administrator and not transferred to a State.

(1) Section 60.44b(f).

(2) Section 60.44b(g).

(3) Section 60.49b(a)(4).

(h) Any affected facility that meets the applicability requirements and is subject to subpart Ea, subpart Eb, subpart AAAA, or subpart CCCC of this part is not subject to this subpart.

(i) Affected facilities (i.e., heat recovery steam generators) that are associated with stationary combustion turbines and that meet the applicability requirements of subpart KKKK of this part are not subject to this subpart. This subpart will continue to apply to all other affected facilities (i.e. heat recovery steam generators with duct burners) that are capable of combusting more than 29 MW (100 MMBtu/h) heat input of fossil fuel. If the affected facility (i.e. heat recovery steam generator) is subject to this subpart, only emissions resulting from combustion of fuels in the steam generating unit are subject to this subpart. (The stationary combustion turbine emissions are subject to subpart GG or KKKK, as applicable, of this part.)

(j) Any affected facility meeting the applicability requirements under paragraph (a) of this section and commencing construction, modification, or reconstruction after June 19, 1986 is not subject to subpart D (Standards of Performance for Fossil-Fuel-Fired Steam Generators, § 60.40).

(k) Any affected facility that meets the applicability requirements and is subject to an EPA approved State or Federal section 111(d)/129 plan implementing subpart Cb or subpart BBBB of this part is not covered by this subpart.

(l) Affected facilities that also meet the applicability requirements under subpart BB of this part (Standards of Performance for Kraft Pulp Mills) are subject to the SO2 and NOX standards under this subpart and the PM standards under subpart BB.

(m) Temporary boilers are not subject to this subpart.

[72 FR 32742, June 13, 2007, as amended at 74 FR 5084, Jan. 28, 2009; 77 FR 9459, Feb. 16, 2012]

Every section in Subpart Db

10 sections, in eCFR order. Each link opens the official text.

  • § 60.40bApplicability and delegation of authority.Amended 2018-09-12
  • § 60.41bDefinitions.Amended 2016-10-31
  • § 60.42bStandard for sulfur dioxide (SO2).Amended 2016-10-31
  • § 60.43bStandard for particulate matter (PM).Amended 2016-10-31
  • § 60.44bStandard for nitrogen oxides (NO2).Amended 2016-10-31
  • § 60.45bCompliance and performance test methods and procedures for sulfur dioxide.Amended 2016-10-31
  • § 60.46bCompliance and performance test methods and procedures for particulate matter and nitrogen oxides.Amended 2019-08-16
  • § 60.47bEmission monitoring for sulfur dioxide.Amended 2016-10-31
  • § 60.48bEmission monitoring for particulate matter and nitrogen oxides.Amended 2016-10-31
  • § 60.49bReporting and recordkeeping requirements.Amended 2016-10-31

Amendment history

Dates on which eCFR records a change to any section of Subpart Db, newest first.

  • 2019-08-16
  • 2018-09-12
  • 2016-10-31

To read the rulemakings behind these dates, search the Federal Register for Subpart Db. New EPA air rules and proposals also appear in the Federal Air Rule Tracker.

AirPermitHub provides educational, engineering, research, and compliance-support information. Information provided by the platform does not constitute legal advice and should not replace review of applicable regulations, permits, agency guidance, or consultation with qualified professionals. Full disclaimer